INVERSE TIME CIRCUIT BREAKERS, 600 A, 600 V AC
|
|||||||
| Circuit Breaker |
Long Time Response Current Settings |
SETTING RANGES ADJUSTABLE INSTANEOUS PICK-UP SETTING |
ADJUSTABLE SHORT TOME DELAY PICK UP SETTING FOR SELECTIVITY IN
NETWORKS TIME DELAY RANGE 0-1000 ms DELAYED |
NORMAL INTERRUPTING CAPACITY 42 kA at 480 V 50/60 HZ 35 kA at 600 V 50/60 HZ |
HIGH INTERRUPTING CAPACITY 100 kA at 480 V 50/60 HZ 50 kA at 600 V 50/60 HZ |
||
WITH FIXED LONG TIME RESPONSE SETTING
|
200 | 1000-9000 | 2 - 12 x Ir | ||||
| 225 | 1000-9000 | 2 - 12 x Ir | |||||
| 250 | 1000-9000 | 2 - 12 x Ir | |||||
| 300 | 1000-9000 | 2 - 12 x Ir | |||||
| 350 | 1000-9000 | 2 - 12 x Ir | |||||
| 400 | 1000-9000 | 2 - 12 x Ir | |||||
| 500 | 1000-9000 | 2 - 12 x Ir | NZM10-600N/ZMVA-500-NA | NZM10-600S/ZMVA-500-NA | |||
| 600 | 1000-9000 | 2 - 12 x Ir | NZM10-600N/ZMVA-600-NA | NZM10-600S/ZMVA-600-NA | |||
WITH ADJUSTABLE LONG TIME RESPONSE SETTINGS
|
200 - 400 | 1000-9000 | 400 - 4800 | ||||
| 300 - 600 | 1000-9000 | 600 - 7200 | NZM10-600N/ZMV-600-NA | NZM10-600S/ZMV-600-NA | |||